50kw Air Cooled Chiller ,Procedure for first start or debugging
A. After finishing electrical wiring, please check especially whether the circuit breaker meet requirements, whether peripheral equipments are connected correctly according to the electric wiring diagram;
B. Compressor oil heater is powered on and heated at least for 8 hours.
C. Check and make sure that all valves of refrigeration system and water valves are fully open, water flow switch and the water inlet valve and so on are in good condition;
Tag-uri populare: Răcitor de apă răcit cu aer 50kw, răcitor de aer industrial de 50kw, 50kw, răcitor industrial de răcire de apă industrial de 50kw, 50kw, răcitor de apă 50kw, 50kw răcitor de apă răcit cu aer, unitate de răcire mică de 50kw, unitate de răcire de aer 50kw, răcitor de aer 50kw, răcitor de apă industrial 50kw